Analisador de Potência Trifásica e Data Logger AEMC PEL 102

    Preço sob consulta

    Estoque: sob consulta


The PEL 102 is a low cost, simple to use, one, two (split phase) and three phase (Y, Δ) power/energy data logger.



This product is ideal for electricians, engineers and contractors doing work in the area of building and system monitoring and upgrades, as well as residential and overall energy audits. All vital energy data is easily measured, recorded, and analyzed. Reports can be generated with confidence with minimal configuration time and effort (Standard and Customizable Reports supplied).

The instrument’s design enables it to be installed inside a load center panel (including the current sensors) allowing the door to close on most panels. The PEL 100 series offers all the essential functions for logging power/energy data from most electrical power networks in use today across the world (17 network set-ups provided). The PEL 100 series energy loggers measure and record three True RMS voltage inputs and current inputs, Watts, VARS, VA and Energy (kWh and kVA). Power Factor (PF), Displacement Power Factor (DPF), Crest Factor, Frequency and THD are calculated and recorded as well. Individual harmonic % information from 1 to the 50th harmonic are recorded at the operator’s choice. All variables are recorded and stored at a one second interval and on user selectable demand intervals from 1 to 60 minutes.


SPECIFICATIONS

MODELS: PEL 102, PEL 103 & PEL 105

GENERAL    
Sampling Frequency: 128 samples per cycle; 50/60Hz (16 samples/cycle 400Hz)
Data Storage Rate: 1 per second (200ms also available on PEL 105)
Demand Period Storage Rate: User selectable (1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30 and 60 minutes)
Recorded Parameters (Single- and Poly-Phase): V, I, W, VA, var, PF, Tan, Wh, VAh, varh, THD (V and I), Individual harmonics (from 1 through 50 per phase); Crest Factor (CF), Cos f / DPF
Event Log: Tracks and records status changes and error messages along with recorded data
Front Panel Indicator LEDs: Bluetooth active, recording in progress, phase connection reversal, overload, battery charging and SD Card status
Storage Capacity: 8GB SD card included / SD cards up to 32GB formatted FAT32 are supported
Voltage Input: PEL 102/103 – 3 input channels; PEL 105 – 4 input channels via 4mm safety banana jacks
Current Input: PEL 102/103 - 3 input channels; PEL 105 – 4 input channels via custom 4 pin jacks that accept AEMC® probes and sensors


ELECTRICAL


VOLTAGE MEASUREMENTRANGERESOLUTION*ACCURACY*
50/60Hz42.5 to 69Hz±0.1Hz
Single-Phase RMS Voltages10 to 1000Vrms0.1V±0.2% Rdg ±0.2V
Phase-to-Phase RMS Voltages17 to 1700Vrms0.1 to 1V±0.2% Rdg ±0.4V
400Hz340 to 460Hz
Single-Phase RMS Voltages10 to 600Vrms0.1V±1% Rdg ±1V
Phase-to-Phase RMS Voltages17 to 1200Vrms0.1 to 1V±1% Rdg ±1V
DC100 to 1000V0.1V±1% Rdg ±3V (typical)
PT RatiosProgrammable from 50V to 650,000V0.01 to 0.1V


CURRENT MEASUREMENTA193*** (PEL 102/103)196A*** (PEL 105)--
Nominal range for current probes¹200mA to 10,000A200mA to 10,000A
CT RatiosProgrammable from 1:1 to 25,000:1 (probe dependent)


POWER MEASUREMENTSRANGERESOLUTION*ACCURACY*
Active Power (P)*-2 to 2GW0.001W±0.5% Rdg ±0.005% Pnom
Reactive Power (Q)*-2 to 2Gvar0.001var±1% Rdg ±0.01% Qnom
Apparent Power (S)*0 to 2GVA0.001VA±0.5% Rdg ±0.005% Snom
Power Factor-1 to 10.001±0.05
Tangent φ (active/reactive power ratio)-3.2 to 3.20.001±0.02


ENERGY MEASUREMENTSRANGERESOLUTION*ACCURACY*
Active Energy (EP)0 to 4 x 10"1Wh±0.5% Rdg
Reactive Energy (EQ)0 to 4 x 10"1varh±2% Rdg
Apparent Energy (ES)0 to 4 x 10"1Vah±0.5% Rdg
THD±655%±655%±655%
Individual Harmonics1 to 50 displayed in percentage; 1 to 7 at 400Hz
External Supply110V/250V (10%) @ 50/60Hz; 400Hz
Power From Phase MeasurementPEL 102/103 requires optional Power Adapter Cat #2137.77; PEL 105 Internal up to 1000Vac
Back-Up Power Source/Charge TimeRechargeable 8.4V NiMH battery pack / Approximately 5 hours
Battery Life30 minutes minimum, 60 minutes typical

¹ (supplied with kit. See chart on Pages 26 and 27 for other probes)


MECHANICAL


Communication Ports: USB 2.0, Ethernet (RJ45), Wireless Bluetooth Class 1 **/ Wi-Fi (PEL 105 only)
Dimension/Weight: 10.08 x 4.92 x 1.46" (256 x 125 x 37mm) / 2.20lbs (1kg) (PEL 102 & PEL 103);  9.8 x 7.8 x 2.6" (250 x 200 x 67mm) / 8.8lbs (4kg) (PEL 105)
Case: Double insulated, rubber over-molded, polycarbonate UL94 V1 rated


DISPLAY
Display Type for Model PEL 103 / PEL 105: 2.63 x 2.16" (67 x 55mm), four line, monochrome, backlit LCD with adjustable brightness and contrast

ENVIRONMENTAL / SAFETY
Operating Temperature/Relative Humidity: 50° to 122°F (10° to 50°C) / up to 85%; 32° to 108.5°F (0° to 42.5°C) / up to 85% (PEL 103 & PEL 105)
Storage Temperature: -4° to 122°F (-20° to 50°C) with batteries; -4° to 158°F (-20° to 70°C) without batteries
Safety Rating/CE Rating: Complies with IEC 61010-1, and IEC 61010-2-030 for 1000V CAT III / 600V CAT IV (PEL 102 & PEL 103)  & 1000V CAT IV (PEL 105), Pollution Degree 2 / Yes
Index of Protection: IP54 non operating (PEL 102 & PEL 103) / IP67 with cover closed (PEL 105)
* Maximum value is current probe dependent.
** Computers with Class II Bluetooth will restrict range to 40ft. Computers without Bluetooth will require a Class I or Class II Bluetooth radio adapter.
*** Maximum current reduced by a factor of 2 for 400Hz fundamental frequency.


User Manual

Datasheet

Brochure

Brochure: Power Quality

Power Analyzer - Current Probe Specification Chart



Escreva um comentário

    Ruim           Bom

Perguntas e respostas

Receba as melhores ofertas e descontos exclusivos! Cadastre seu nome e e-mail aqui.

Acompanhe a Signum Technologies

Voltar ao Inicio
Signum Technologies © 2024
Desenvolvido por Ellis Agência Web Agência Ellis
Segurança e certificações
Segurança e certificações Segurança e certificações Segurança e certificações