Fonte de Alimentação CC de Alta Tensão Fug Série Professional HCP
Preço sob consulta
HIGH VOLTAGE POWER SUPPLIES - Switch Mode Regulation
Series HCP from 3.5kV to 300kV / 14W to 15kW
In principle, the rectified line voltage drives a square wave generator of fixed frequency, whose AC voltage is transformed, rectified and filtered, producing the output voltage. For regulation, the square wave voltage is pulse width modulated. A low residual ripple of the output voltage, together with a high stability, high regulation speed and a low stored energy are all achieved by virtue of the high switching frequency.
FEATURES:
- Compact size and light weight
- Efficiency approx. 90%
- For units from 12.5kV nominal voltage on, all HV components are moulded in (removable) silicon
- Short-circuit & flashover proof
- Unlimited operation with rated current in a short-circuit condition
- Unlimited operation with rated power
- Voltage and current regulation with automatic sharp transition, control modes indicated by LEDs
- Adjustable overvoltage protection (limitation of set value)
- 4½ digit DVM‘s for voltage and current for all models
- Voltage and current setting by means of 10-turn potentiometers with precision scale; the adjusting knob can be locked
- Indication of set point values by means of button for switchover of the displays
- Set point adjustment possible with locked output, release of output voltage by means of „ON“ / „OFF“ switch
- Suitable also for inductive and capacitive loads
- Suitable for photomultipliers
POWER
Power range up to 15.000W
VOLTAGE
Output voltage 125V up to 300.000V, continuously adjustable from zero to maximum
APPLICATIONS
Electron beam and ion beam generation
Electrostatic applications
Mass spectrometry
Electron microscopy
Electron lithography
Electron beam welding
Test and manufacturing of semiconductor materials and electron tubes
SPECIAL FEATURES
Switch mode regulation
Low ripple
High stability
High regulation speed
Low stored energy
DESIGN:
- ½19" or 19" table-top case (depending on output voltage and power).
- 19" Rack-adapters for mounting into a 19" rack are available as accessory.
OUTPUT:
- Output isolation: The required output polarity must be stated with the order. The requested output polarity will then be available at the HV connector and the “0V” terminal will be firmly connected to earth. If required, the „0V“ terminal can be made floating against earth up to ± 300V. A polarity reversal switch is optionally available.
- Output terminals: All output terminals are located at the rear side of the unit. High voltage connectors with the appropriate dielectric strength are delivered with the power supply. For nominal voltage of 65kV and higher the HV- plug will be delivered ready mounted to 3m cable.
TECHNICAL DATA:
- Mains connection:
>> Up to 1400W nominal power: 230V ±10% 47Hz to 63Hz
>> For 2800W and higher: 400V ±10% 47Hz to 63Hz, three-phase
- Ambient temperature: 0°C to +40°C
The following data applies for voltage and current regulation, and refers to the rated value (unless otherwise stated):
- Setting range: from approx. 0,1% to 100%
- Setting resolution: ±1 x 10-4
- Residual ripple (0-10MHz): <1 x 10-4pp + 50mVpp, typ. 5 x 10-5pp
- Recovery time:
>> Voltage control: <1ms for load changes from 10% to 100% or from 100% to 10%
>> Current control: <10ms for load changes causing an output change of less than 10% of the rated voltage
- Setting time at nominal load: <500ms for changes of the output voltage from 10% to 90% or 90% to 10%
- Discharge time constant for output without load: approx. 2sec. to 10sec., depending on type
- Deviation:
>> For ±10% mains voltage variation: <± 1 x 10-5
>> For no load / full load: <2 x 10-4
>> Over 8 hours under constant conditions: <±1 x 10-4
>> Within the temperature range: <±1,5 x 10-4/K
POSSIBLE OPTIONS:
- Coarse/fine-potentiometers (99% / 1%) for more accurate adjustment of voltage and / or current
- Analog programming
- Analog programming, floating
- Computer interfaces - IEEE 488, RS 232, RS 422, Profibus DP, USB, LAN (more on request)
- Electronically controlled polarity reversal switch (Up to 35kV remotely controllable when ordered with a programming or interface, for higher voltages, on request). Please specify the output polarity, when ordering without polarity reversal switch.
- Lower ripple
- Higher stability
- Lower stored energy
- Power limitation
TYPE OVERVIEW
TYPE | VOLTAGE | CURRENT | WIDTH | HEIGHT | DEPTH | WEIGHT |
HCP 14 - 3500 | • 0 - 3500 V | 0 - 4 mA | ½19" / 222 mm | 3 U / 133 mm | 350 mm | 3 kg |
HCP 35 - 3500 | • 0 - 3500 V | 0 - 10 mA | ½19" / 222 mm | 3 U / 133 mm | 350 mm | 4 kg |
HCP 140 - 3500 | • 0 - 3500 V | 0 - 40 mA | ½19" / 222 mm | 3 U / 133 mm | 350 mm | 6 kg |
HCP 350 - 3500 | • 0 - 3500 V | 0 - 100 mA | ½19" / 222 mm | 3 U / 133 mm | 450 mm | 7 kg |
HCP 700 - 3500 | • 0 - 3500 V | 0 - 200 mA | 19" / 443 mm | 3 U / 133 mm | 350 mm | 11 kg |
HCP 1400 - 3500 | • 0 - 3500 V | 0 - 400 mA | 19" / 443 mm | 3 U / 133 mm | 450 mm | 13 kg |
HCP 2800 - 3500 | 3) 0 - 3500 V | 0 - 800 mA | 19" / 443 mm | 3 U / 133 mm* | 550 mm** | 25 kg |
HCP 5000 - 3500 | 3) 0 - 3500 V | 0 - 1,5 A | 19" / 443 mm | 6 U / 266 mm | 650 mm | 40 kg |
HCP 10000 - 3500 | 3) 0 - 3500 V | 0 - 3 A | 19" / 443 mm | 9 U / 399 mm | 650 mm | 75 kg |
HCP 15000 - 3500 | 3) 0 - 3500 V | 0 - 4,5 A | 19" / 443 mm | 12 U / 535 mm | 650 mm | 110 kg |
HCP 14 - 6500 | • 0 - 6500 V | 0 - 2 mA | ½19" / 222 mm | 3 U / 133 mm | 350 mm | 3 kg |
HCP 35 - 6500 | • 0 - 6500 V | 0 - 5 mA | ½19" / 222 mm | 3 U / 133 mm | 350 mm | 4 kg |
HCP 140 - 6500 | • 0 - 6500 V | 0 - 20 mA | ½19" / 222 mm | 3 U / 133 mm | 350 mm | 6 kg |
HCP 350 - 6500 | • 0 - 6500 V | 0 - 50 mA | ½19" / 222 mm | 3 U / 133 mm | 450 mm | 7 kg |
HCP 700 - 6500 | • 0 - 6500 V | 0 - 100 mA | 19" / 443 mm | 3 U / 133 mm | 350 mm | 11 kg |
HCP 1400 - 6500 | • 0 - 6500 V | 0 - 200 mA | 19" / 443 mm | 3 U / 133 mm | 450 mm | 13 kg |
HCP 2800 - 6500 | 3) 0 - 6500 V | 0 - 400 mA | 19" / 443 mm | 3 U / 133 mm* | 650 mm | 25 kg |
HCP 5000 - 6500 | 3) 0 - 6500 V | 0 - 750 mA | 19" / 443 mm | 6 U / 266 mm | 650 mm | 40 kg |
HCP 10000 - 6500 | 3) 0 - 6500 V | 0 - 1,5 A | 19" / 443 mm | 9 U / 399 mm | 650 mm | 75 kg |
HCP 15000 - 6500 | 3) 0 - 6500 V | 0 - 2,3 A | 19" / 443 mm | 12 U / 535 mm | 650 mm | 110 kg |
HCP 14 - 12500 | • 0 - 12500 V | 0 - 1 mA | ½19" / 222 mm | 3 U / 133 mm | 350 mm | 4 kg |
HCP 35 - 12500 | • 0 - 12500 V | 0 - 2,5 mA | ½19" / 222 mm | 3 U / 133 mm | 350 mm | 5 kg |
HCP 140 - 12500 | • 0 - 12500 V | 0 - 10 mA | ½19" / 222 mm | 3 U / 133 mm | 350 mm | 7 kg |
HCP 350 - 12500 | • 0 - 12500 V | 0 - 25 mA | 19" / 443 mm | 3 U / 133 mm | 450 mm | 11 kg |
HCP 700 - 12500 | • 0 - 12500 V | 0 - 50 mA | 19" / 443 mm | 3 U / 133 mm | 550 mm | 16 kg |
HCP 1400 - 12500 | • 0 - 12500 V | 0 - 100 mA | 19" / 443 mm | 3 U / 133 mm | 650 mm | 21 kg |
HCP 2800 - 12500 | 3) 0 - 12500 V | 0 - 200 mA | 19" / 443 mm | 6 U / 266 mm | 550 mm | 35 kg |
HCP 5000 - 12500 | 3) 0 - 12500 V | 0 - 400 mA | 19" / 443 mm | 6 U / 266 mm | 650 mm | 40 kg |
HCP 10000 - 12500 | 3) 0 - 12500 V | 0 - 800 mA | 19" / 443 mm | 9 U / 399 mm | 650 mm | 75 kg |
HCP 15000 - 12500 | 3) 0 - 12500 V | 0 - 1,2 A | 19" / 443 mm | 12 U / 535 mm | 650 mm | 110 kg |
HCP 14 - 20000 | • 0 - 20000 V | 0 - 0,6 mA | ½19" / 222 mm | 3 U / 133 mm | 350 mm | 4 kg |
HCP 35 - 20000 | • 0 - 20000 V | 0 - 1,5 mA | ½19" / 222 mm | 3 U / 133 mm | 350 mm | 5 kg |
HCP 140 - 20000 | • 0 - 20000 V | 0 - 6 mA | ½19" / 222 mm | 3 U / 133 mm | 350 mm | 7 kg |
HCP 350 - 20000 | • 0 - 20000 V | 0 - 15 mA | 19" / 443 mm | 3 U / 133 mm | 450 mm | 11 kg |
HCP 700 - 20000 | • 0 - 20000 V | 0 - 30 mA | 19" / 443 mm | 3 U / 133 mm | 550 mm | 16 kg |
HCP 1400 - 20000 | 0 - 20000 V | 0 - 60 mA | 19" / 443 mm | 3 U / 133 mm | 650 mm | 21 kg |
HCP 2800 - 20000 | 3) 0 - 20000 V | 0 - 120 mA | 19" / 443 mm | 6 U / 266 mm | 650 mm | 35 kg |
HCP 4200 - 20000 | 3) 0 - 20000 V | 0 - 200 mA | 19" / 443 mm | 6 U / 266 mm | 650 mm | 45 kg |
HCP 35 - 35000 | • 0 - 35000 V | 0 - 1 mA | 19" / 443 mm | 3 U / 133 mm | 450 mm | 10 kg |
HCP 140 - 35000 | • 0 - 35000 V | 0 - 4 mA | 19" / 443 mm | 3 U / 133 mm | 450 mm | 12 kg |
HCP 350 - 35000 | • 0 - 35000 V | 0 - 10 mA | 19" / 443 mm | 3 U / 133 mm | 450 mm | 17 kg |
HCP 700 - 35000 | • 0 - 35000 V | 0 - 20 mA | 19" / 443 mm | 3 U / 133 mm | 550 mm | 20 kg |
HCP 1400 - 35000 | 0 - 35000 V | 0 - 40 mA | 19" / 443 mm | 3 U / 133 mm | 650 mm | 25 kg |
HCP 2800 - 35000 | 3) 0 - 35000 V | 0 - 80 mA | 19" / 443 mm | 6 U / 266 mm | 650 mm | 45 kg |
HCP 4200 - 35000 | 3) 0 - 35000 V | 0 - 120 mA | 19" / 443 mm | 7 U / 310 mm | 650 mm | 50 kg |
HCP 35 - 65000 | 0 - 65000 V | 0 - 0,5 mA | 19" / 443 mm | 3 U / 133 mm* | 450 mm** | 17 kg |
HCP 140 - 65000 | 0 - 65000 V | 0 - 2 mA | 19" / 443 mm | 3 U / 133 mm* | 450 mm** | 21 kg |
HCP 350 - 65000 | 0 - 65000 V | 0 - 5 mA | 19" / 443 mm | 6 U / 266 mm* | 450 mm** | 45 kg |
HCP 700 - 65000 | 0 - 65000 V | 0 - 10 mA | 19" / 443 mm | 8 U / 355 mm* | 550 mm** | 55 kg |
HCP 1400 - 65000 | 0 - 65000 V | 0 - 20 mA | 19" / 443 mm | 9 U / 399 mm* | 550 mm** | 70 kg |
HCP 2800 - 65000 | 3) 0 - 65000 V | 0 - 40 mA | 19" / 443 mm | 9 U / 399 mm* | 550 mm** | 80 kg |
HCP 140 - 100000 | 0 - 100000 V | 0 - 1 mA | 19" / 443 mm | 5 U / 221 mm | 550 mm | 50 kg |
HCP 350 - 100000 | 0 - 100000 V | 0 - 3 mA | 19" / 443 mm | 5 U / 221 mm | 550 mm | 55 kg |
HCP 700 - 100000 | 0 - 100000 V | 0 - 6 mA | 19" / 443 mm | 8 U / 355 mm | 550 mm | 73 kg |
HCP 1400 - 100000 | 0 - 100000 V | 0 - 12 mA | 19" / 443 mm | 9 U / 399 mm | 550 mm | 90 kg |
HCP 140 - 150000 | 0 - 150000 V | 0 - 0,5 mA | 19" / 443 mm | 10 U /433 mm | 750 mm | 110 kg |
HCP 350 - 150000 | 0 - 150000 V | 0 - 2 mA | 19" / 443 mm | 10 U /433 mm | 750 mm | 130 kg |
HCP 700 - 150000 | 0 - 150000 V | 0 - 4 mA | 19" / 443 mm | 10 U /433 mm | 750 mm | 140 kg |
HCP 1400 - 150000 | 0 - 150000 V | 0 - 8 mA | 19" / 443 mm | 12 U /535 mm | 750 mm | 160 kg |
HCP 140 - 200000 | 0 - 200000 V | 0 - 0,75 mA | 19" / 443 mm | 12 U /535 mm | 750 mm | 160 kg |
HCP 350 - 200000 | 0 - 200000 V | 0 - 1,5 mA | 19" / 600 mm | 29 U /1500 mm | 600 mm | 180 kg |
HCP 700 - 200000 | 0 - 200000 V | 0 - 3 mA | 19" / 600 mm | 38 U /2000 mm | 800 mm | 200 kg |
HCP 1400 - 200000 | 0 - 200000 V | 0 - 6 mA | 19" / 600 mm | 38 U /2000 mm | 800 mm | 220 kg |
HCP 140 - 300000 | 0 - 300000 V | 0 - 0,3 mA | 19" / 600 mm | 29 U /1500 mm | 750 mm | 180 kg |
HCP 350 - 300000 | 0 - 300000 V | 0 - 1 mA | 19" / 600 mm | 38 U /1500 mm | 600 mm | 200 kg |
HCP 700 - 300000 | 0 - 300000 V | 0 - 2 mA | 19" / 600 mm | 38 U /2000 mm | 800 mm | 220 kg |
HCP 1400 - 300000 | 0 - 300000 V | 0 - 4 mA | 19" / 600 mm | 38 U /2000 mm | 800 mm | 250 kg |
*) With polarity reversal switch these units will be 2U higher.
**) With polarity reversal switch these units will be 100mm deeper
3) connection three-phase
• short term delivery (components on stock)
Mating high voltage connectors are included in the scope of delivery.
All units up to 35kV optionally available with electronically controlled polarity reversal switch and for 65kV with manually operated polarity reversal switch.